16 Input Notice Relay

Login / Sign Up to Get a Quote and Place an Order

SKU: ISP-16 Basic-1
  • 16 Channel LED Lighting Technology.
  • Communication and event recording options.
  • Safe operation under electromagnetic noise.
  • Ability to work at different voltage levels. (24/48, 110 and 220 VDC)
  • Easy Programming with ISPsimTM Software.
  • Ability to make relay output selections for each channel with the buttons on the front panel.
  • Isolated RS485 port and ModbusRTU protocol support.
  • High-quality, long-lasting power unit with temperature, short circuit, overcurrent/voltage protection.
Login / Sign Up
  • Check Mark 5 Years Warranty
  • Check Mark 1 Hour Online Product Training
  • Check Mark Made In Turkey
Secure Payment
SKU: ISP-16 Basic-1 Category:

TELEPRO-ISP-16 Alarm Announcer is our product that offers flexible, functional and reliable solutions in protection and control automation systems.

Our product, which combines quality, compact and original design with low cost, is a unique design with optional communication and optional event recording option.

Each of the 16 entrances is insulated. The opto-coupler is shielded with harmoic suppressors and noise filtering software. It can be used safely in environments with high electromagnetic noise, which is constantly encountered in the usage environments of the device.

Horn and bell selections can be easily adjusted with the buttons on the front panel, and all features can be configured with the ISPsimTM software in models with communication.

Our models, which include an optional event recorder, have the ability to record events in 1 ms resolution.

For electromagnetic noise environments, response and release times can be adjusted between 3-250ms. (In models with communication)

The optional RS485 communication port supports the ModbusRTU protocol and can be easily integrated into SCADA systems.

Thanks to the special labeling template provided by TELEPRO® , the ISP-16 can be easily labeled.

LED LIGHTING

Energy-saving LED lighting, which provides high-quality images, is offered as standard in all our models. Featuring isolated LED positioning for each indicator, the ISP16 completely eliminates confusion and provides easy operation with its ultra-bright image.

ENTRIES

All Inputs are opto coupler insulated. The possibility of false alarms is completely eliminated. The maximum input current is designed as 5mA, and the input voltage is 110Vdc.

RELAY OUTPUTS

The TELEPRO-ISP16 Basic includes two Normally Open 1-FormA type dry contact relay outputs as standard. Outputs are assigned to HORN or BELL options. All channels can be set to these output options from the front panel buttons.

In addition, there is a FAULT relay with common end NC / NO outputs that are activated in case of internal system failures.

RESPONSE AND QUIT TIMES

Response and release times are available for flexible and reliable operation in different protection manoeuvres in the system. It is used as 5ms for response time and 20ms for release time.

HIGH-QUALITY POWER UNIT

The TELEPRO-ISP16 Basic can be operated safely in the 110V DC range. Our power supplies provide a long life guarantee with their short-circuit, overcurrent/voltage and temperature-protected designs.

DISPLAY & LABELING

It has a membrane-featured, high-quality front panel design. Our easy-to-change printer printed labeling system has a user-friendly design with a screen width of 46.5×10.5 mm allocated for each channel.

The windows of each channel are named with the label template provided by TELEPRO® in the computer environment. Label information can be easily changed at any time.

CHASSIS AND ASSEMBLY

The TELEPRO-ISP16 Basic is available in a panel-mounted chassis configuration. The protection class on the front panel side of our standard cases is IP51. In standard dimensions (144x144x57 mm) and weighing 585 gr, it can be assembled/disassembled quickly and safely with its easy-to-use screw mounting system.

EASY TO USE

In TELEPRO-ISP16 Basic, 16 potential contacts from relays in the field are activated by connecting them to the device input terminals.

Each channel can be assigned to the HORN or BELL relay according to the operator’s preference. These settings also make a difference in LED lighting. In the BELL assignment, the corresponding channel is illuminated in GREEN, and in the case of a HORN call, it is illuminated in RED. (Optional Red/Yellow Option available)

The connection and other details are detailed in the installation guide provided with our devices.

Weight0.443 kg
Dimensions183 × 107 × 153 cm
Supply Voltage

24-48Vdc, Voltage Range 18-60Vdc, 110Vdc, Voltage Range 88-132Vdc, 220Vdc, Voltage Range 176-242Vdc

Besleme Gücü

5w

Saha Kontak Girişi

16 Programmable Digital Inputs – Normally Open (N.O.)

Giriş Akımı ( Kanal Başına )

Max. 5 mA

Giriş Direnci (min)

75kΩ

Transiyent Voltaj

Common Mode: 1kV – Serial Mode: 2kV

Bırakma Süresi

20 ms

Bağlantı Tipi

Plug-in Type Terminal Block

Kablo Kesiti

12 AWG (2.5 mm)

Kontak Çıkışları

250Vdc-0.1A

Korna Rölesi

1-Form-A dry contact relay (SPST) (NO)

Zil Rölesi

1-Form-A dry contact relay (SPST) (NO)

Arıza Rölesi

1-Form-C dry contact relay (SPDT) (NO/NC)

Kontrol Butonları

Reset, Test, Ack, Horn (with Led status indicator)

Ön Panel

2 Layer

Işıklı Uyarı

5mm 2 Color (Red/Green)

Sesli Uyarı

23mm Buzzer 75 dbA

Korna – Zil Konfigürasyonu

Front Panel Buttons

Kasa Tipi

Panel type

Ölçü(ExBXD)

144x144x57 mm

Pano Bağlantısı

Snap Screw Type

Koruma Sınıfı

IP51 (front panel side)

Çalışma sıcaklığı

-20 +55 C

Depolama Sıcaklığı

-25 C … +80 oC

Ambalaj Ölçüleri(ExBxD)

183x107x153 mm